Skip to Content

Dry cooler BC/BD-191LB1-B04 C

Dry cooler BC/BD-191LB1-B04 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-191LB1-B04 C

Heat rejection i
62.97 kW
Air flow
25,923 m³/h
Fans
1 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 25,923 m³/h
External surface 135.7 m²
Inner volume 16.4 dm³
Fin materialAluminium
Net weight 225 kg
Fans
Quantity 1
Diameter 910 mm
Speed 840 rpm
Power 2,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 59.0 dB(A)
Sound power 90.5 dB(A)
Energy class E
Connections
Inlet 1 1/2"
Outlet 1 1/2"
Defrost
BC/BD-191LB1-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
62.965 kW Fluid flow 10.93 m³/h Pressure drop 53.6 kPa
Heat rejection · Low speed (Y)
50.648 kW Fluid flow 8.79 m³/h Pressure drop 36.3 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 35.28 not rated not rated not rated not rated not rated
40 62.97 35.58 not rated not rated not rated not rated
45 90.06 63.11 35.83 not rated not rated not rated
50 116.98 90.08 63.24 36.06 not rated not rated
55 143.82 116.89 90.12 63.38 36.28 not rated
60 170.61 143.62 116.83 90.18 63.53 36.50

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 28.57 not rated not rated not rated not rated not rated
40 50.65 28.81 not rated not rated not rated not rated
45 72.19 50.76 29.03 not rated not rated not rated
50 93.57 72.21 50.87 29.22 not rated not rated
55 114.87 93.50 72.24 51.00 29.41 not rated
60 136.13 114.72 93.46 72.30 51.14 29.60

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 62.965 10.93 53.6
Low speed (Y) 50.648 8.79 36.3

Dimensions

Dimension drawing of BC/BD-191LB1-B04 C
Dimension drawing
Dimensions as drawn
A 2100 mm
B 1450 mm
C 1230 mm
F 1150 mm
G 550 mm
E 1850 mm
H 1750 mm
I 1180 mm
K 2400 mm
D IN 1 1/2"
D OUT 1 1/2"
Overall [mm]
Length 2400 mm
Width 1230 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.