Skip to Content

Dry cooler BC/BD-191MB5-B04 C

Dry cooler BC/BD-191MB5-B04 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-191MB5-B04 C

Heat rejection i
67.90 kW
Air flow
27,978 m³/h
Fans
1 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 27,978 m³/h
External surface 157.6 m²
Inner volume 23.4 dm³
Fin materialAluminium
Net weight 257 kg
Fans
Quantity 1
Diameter 910 mm
Speed 840 rpm
Power 2,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 58.0 dB(A)
Sound power 90.0 dB(A)
Energy class E
Connections
Inlet 2"
Outlet 2"
Defrost
BC/BD-191MB5-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
67.899 kW Fluid flow 11.78 m³/h Pressure drop 69.3 kPa
Heat rejection · Low speed (Y)
55.476 kW Fluid flow 9.63 m³/h Pressure drop 48.5 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 38.84 not rated not rated not rated not rated not rated
40 67.90 39.02 not rated not rated not rated not rated
45 96.39 67.92 39.17 not rated not rated not rated
50 124.69 96.27 67.94 39.30 not rated not rated
55 152.92 124.45 96.18 67.97 39.44 not rated
60 181.10 152.55 124.25 96.12 68.03 39.59

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 31.91 not rated not rated not rated not rated not rated
40 55.48 32.05 not rated not rated not rated not rated
45 78.53 55.48 32.17 not rated not rated not rated
50 101.42 78.41 55.48 32.28 not rated not rated
55 124.23 101.19 78.32 55.50 32.39 not rated
60 147.01 123.90 101.00 78.26 55.55 32.51

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 67.899 11.78 69.3
Low speed (Y) 55.476 9.63 48.5

Dimensions

Dimension drawing of BC/BD-191MB5-B04 C
Dimension drawing
Dimensions as drawn
A 2750 mm
B 1450 mm
C 1230 mm
F 1150 mm
G 550 mm
E 2500 mm
H 2400 mm
I 1180 mm
K 3050 mm
D IN 2"
D OUT 2"
Overall [mm]
Length 3050 mm
Width 1230 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.