BC/BD-380HC5-B03 C
79.72 kW
Defrost: None
Product code: BC/BD-191MC5-B04 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 27,202 m³/h |
|---|---|
| External surface | 210.2 m² |
| Inner volume | 29.3 dm³ |
| Fin material | Aluminium |
| Net weight | 273 kg |
| Quantity | 1 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 2,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 90.0 dB(A) |
| Energy class | E |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BC/BD-191MC5-B04 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 46.14 | not rated | not rated | not rated | not rated | not rated |
| 40 | 79.81 | 46.31 | not rated | not rated | not rated | not rated |
| 45 | 112.71 | 79.76 | 46.45 | not rated | not rated | not rated |
| 50 | 145.36 | 112.47 | 79.72 | 46.59 | not rated | not rated |
| 55 | 177.89 | 144.94 | 112.26 | 79.71 | 46.73 | not rated |
| 60 | 210.37 | 177.29 | 144.58 | 112.12 | 79.74 | 46.89 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 37.13 | not rated | not rated | not rated | not rated | not rated |
| 40 | 63.79 | 37.27 | not rated | not rated | not rated | not rated |
| 45 | 89.76 | 63.75 | 37.40 | not rated | not rated | not rated |
| 50 | 115.51 | 89.56 | 63.72 | 37.52 | not rated | not rated |
| 55 | 141.16 | 115.17 | 89.41 | 63.73 | 37.65 | not rated |
| 60 | 166.75 | 140.68 | 114.90 | 89.32 | 63.77 | 37.79 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 79.811 | 13.85 | 58.2 |
| Low speed (Y) | 63.787 | 11.07 | 39.0 |
| A | 2750 mm |
|---|---|
| B | 1450 mm |
| C | 1230 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 2500 mm |
| H | 2400 mm |
| I | 1180 mm |
| K | 3050 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 3050 mm |
|---|---|
| Width | 1230 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.