BC/BD-t-2X250AC5-B09 C
94.31 kW
Defrost: None
Product code: BC/BD-191MD1-B04 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 26,016 m³/h |
|---|---|
| External surface | 310.2 m² |
| Inner volume | 35.1 dm³ |
| Fin material | Aluminium |
| Net weight | 296 kg |
| Quantity | 1 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 2,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 90.5 dB(A) |
| Energy class | E |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BC/BD-191MD1-B04 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 55.53 | not rated | not rated | not rated | not rated | not rated |
| 40 | 94.31 | 55.67 | not rated | not rated | not rated | not rated |
| 45 | 131.98 | 94.14 | 55.79 | not rated | not rated | not rated |
| 50 | 169.31 | 131.54 | 93.98 | 55.91 | not rated | not rated |
| 55 | 206.47 | 168.61 | 131.17 | 93.90 | 56.06 | not rated |
| 60 | 243.53 | 205.52 | 168.03 | 130.91 | 93.91 | 56.26 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 43.24 | not rated | not rated | not rated | not rated | not rated |
| 40 | 72.76 | 43.36 | not rated | not rated | not rated | not rated |
| 45 | 101.36 | 72.63 | 43.46 | not rated | not rated | not rated |
| 50 | 129.65 | 101.01 | 72.52 | 43.56 | not rated | not rated |
| 55 | 157.79 | 129.10 | 100.73 | 72.47 | 43.68 | not rated |
| 60 | 185.86 | 157.06 | 128.67 | 100.55 | 72.49 | 43.85 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 94.312 | 16.37 | 55.7 |
| Low speed (Y) | 72.762 | 12.62 | 35.0 |
| A | 2750 mm |
|---|---|
| B | 1450 mm |
| C | 1230 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 2500 mm |
| H | 2400 mm |
| I | 1180 mm |
| K | 3050 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 3050 mm |
|---|---|
| Width | 1230 mm |
| Height | 1450 mm |