Skip to Content

Dry cooler BC/BD-280AD5-B03 C

Dry cooler BC/BD-280AD5-B03 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-280AD5-B03 C

Heat rejection i
63.84 kW
Air flow
15,739 m³/h
Fans
2 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 15,739 m³/h
External surface 347.8 m²
Inner volume 44.9 dm³
Fin materialAluminium
Net weight 379 kg
Fans
Quantity 2
Diameter 800 mm
Speed 435 rpm
Power 600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 12
Acoustic
Sound pressure 35.0 dB(A)
Sound power 67.0 dB(A)
Energy class C
Connections
Inlet 1 1/2"
Outlet 1 1/2"
Defrost
BC/BD-280AD5-B03 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
63.838 kW Fluid flow 11.07 m³/h Pressure drop 71.5 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
48.021 kW Fluid flow 8.33 m³/h Pressure drop 43.0 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 38.72 not rated not rated not rated not rated not rated
40 63.84 38.75 not rated not rated not rated not rated
45 88.26 63.72 38.80 not rated not rated not rated
50 112.45 88.01 63.65 38.88 not rated not rated
55 136.54 112.08 87.84 63.65 38.98 not rated
60 160.56 136.04 111.81 87.77 63.72 39.15

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 29.45 not rated not rated not rated not rated not rated
40 48.02 29.51 not rated not rated not rated not rated
45 66.04 47.98 29.57 not rated not rated not rated
50 83.87 65.92 47.98 29.66 not rated not rated
55 101.62 83.68 65.86 48.03 29.78 not rated
60 119.32 101.36 83.57 65.89 48.15 29.95

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 63.838 11.07 71.5
Low speed (Y) 48.021 8.33 43.0

Dimensions

Dimension drawing of BC/BD-280AD5-B03 C
Dimension drawing
Dimensions as drawn
A 2750 mm
B 1450 mm
C 1240 mm
F 1150 mm
G 550 mm
E 2500 mm
H 1200 mm
I 1190 mm
K 3050 mm
D IN 1 1/2"
D OUT 1 1/2"
Overall [mm]
Length 3050 mm
Width 1240 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.