Skip to Content

Dry cooler BC/BD-280CB1-B03 C

Dry cooler BC/BD-280CB1-B03 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-280CB1-B03 C

Heat rejection i
71.42 kW
Air flow
19,840 m³/h
Fans
2 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 19,840 m³/h
External surface 360.4 m²
Inner volume 43.0 dm³
Fin materialAluminium
Net weight 413 kg
Fans
Quantity 2
Diameter 800 mm
Speed 435 rpm
Power 600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 12
Acoustic
Sound pressure 35.0 dB(A)
Sound power 67.0 dB(A)
Energy class B
Connections
Inlet 2"
Outlet 2"
Defrost
BC/BD-280CB1-B03 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
71.421 kW Fluid flow 12.39 m³/h Pressure drop 40.6 kPa
Heat rejection · Low speed (Y)
56.058 kW Fluid flow 9.72 m³/h Pressure drop 26.3 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 42.13 not rated not rated not rated not rated not rated
40 71.42 42.21 not rated not rated not rated not rated
45 99.91 71.26 42.27 not rated not rated not rated
50 128.15 99.55 71.12 42.34 not rated not rated
55 156.26 127.58 99.24 71.03 42.43 not rated
60 184.31 155.51 127.11 99.01 71.01 42.55

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 33.38 not rated not rated not rated not rated not rated
40 56.06 33.45 not rated not rated not rated not rated
45 78.07 55.95 33.52 not rated not rated not rated
50 99.85 77.81 55.88 33.60 not rated not rated
55 121.53 99.45 77.61 55.85 33.70 not rated
60 143.16 121.00 99.14 77.49 55.89 33.83

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 71.421 12.39 40.6
Low speed (Y) 56.058 9.72 26.3

Dimensions

Dimension drawing of BC/BD-280CB1-B03 C
Dimension drawing
Dimensions as drawn
A 3850 mm
B 1450 mm
C 1240 mm
F 1150 mm
G 550 mm
E 3600 mm
H 1750 mm
I 1190 mm
K 4150 mm
D IN 2"
D OUT 2"
Overall [mm]
Length 4150 mm
Width 1240 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.