Skip to Content

Dry cooler BC/BD-280HC5-B03 C

Dry cooler BC/BD-280HC5-B03 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-280HC5-B03 C

Heat rejection i
53.16 kW
Air flow
15,962 m³/h
Fans
2 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 15,962 m³/h
External surface 183.9 m²
Inner volume 24.1 dm³
Fin materialAluminium
Net weight 318 kg
Fans
Quantity 2
Diameter 800 mm
Speed 435 rpm
Power 600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 12
Acoustic
Sound pressure 35.0 dB(A)
Sound power 67.0 dB(A)
Energy class C
Connections
Inlet 1 1/2"
Outlet 1 1/2"
Defrost
BC/BD-280HC5-B03 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
53.160 kW Fluid flow 9.23 m³/h Pressure drop 77.4 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
41.086 kW Fluid flow 7.13 m³/h Pressure drop 49.0 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 31.41 not rated not rated not rated not rated not rated
40 53.16 31.52 not rated not rated not rated not rated
45 74.39 53.18 31.63 not rated not rated not rated
50 95.45 74.33 53.22 31.74 not rated not rated
55 116.43 95.31 74.31 53.29 31.87 not rated
60 137.37 116.23 95.24 74.35 53.41 32.03

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 24.47 not rated not rated not rated not rated not rated
40 41.09 24.58 not rated not rated not rated not rated
45 57.26 41.13 24.69 not rated not rated not rated
50 73.29 57.26 41.20 24.81 not rated not rated
55 89.26 73.25 57.30 41.30 24.94 not rated
60 105.19 89.18 73.27 57.39 41.44 25.10

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 53.160 9.23 77.4
Low speed (Y) 41.086 7.13 49.0

Dimensions

Dimension drawing of BC/BD-280HC5-B03 C
Dimension drawing
Dimensions as drawn
A 2450 mm
B 1450 mm
C 1230 mm
F 1150 mm
G 550 mm
E 2200 mm
H 1050 mm
I 1180 mm
K 2750 mm
D IN 1 1/2"
D OUT 1 1/2"
Overall [mm]
Length 2750 mm
Width 1230 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.