BC/BD-2X163CD1-B19 C
74.08 kW
Defrost: None
Product code: BC/BD-280KC1-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 19,102 m³/h |
|---|---|
| External surface | 361.9 m² |
| Inner volume | 40.0 dm³ |
| Fin material | Aluminium |
| Net weight | 409 kg |
| Quantity | 2 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 35.0 dB(A) |
|---|---|
| Sound power | 67.0 dB(A) |
| Energy class | B |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BC/BD-280KC1-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 44.72 | not rated | not rated | not rated | not rated | not rated |
| 40 | 74.18 | 44.71 | not rated | not rated | not rated | not rated |
| 45 | 102.86 | 73.95 | 44.71 | not rated | not rated | not rated |
| 50 | 131.28 | 102.43 | 73.77 | 44.73 | not rated | not rated |
| 55 | 159.57 | 130.65 | 102.08 | 73.64 | 44.77 | not rated |
| 60 | 187.80 | 158.76 | 130.14 | 101.82 | 73.60 | 44.88 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 34.63 | not rated | not rated | not rated | not rated | not rated |
| 40 | 56.98 | 34.61 | not rated | not rated | not rated | not rated |
| 45 | 78.67 | 56.77 | 34.60 | not rated | not rated | not rated |
| 50 | 100.14 | 78.30 | 56.61 | 34.61 | not rated | not rated |
| 55 | 121.52 | 99.62 | 78.00 | 56.50 | 34.65 | not rated |
| 60 | 142.85 | 120.85 | 99.20 | 77.79 | 56.46 | 34.74 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 74.182 | 12.86 | 70.1 |
| Low speed (Y) | 56.976 | 9.88 | 43.9 |
| A | 3850 mm |
|---|---|
| B | 1450 mm |
| C | 1230 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 3600 mm |
| H | 1750 mm |
| I | 1180 mm |
| K | 4150 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 4150 mm |
|---|---|
| Width | 1230 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.