BC/BD-t-563AA1-B01 C
113.73 kW
Defrost: None
Product code: BC/BD-280MB5-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 42,905 m³/h |
|---|---|
| External surface | 315.3 m² |
| Inner volume | 45.2 dm³ |
| Fin material | Aluminium |
| Net weight | 458 kg |
| Quantity | 2 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 3,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 51.0 dB(A) |
|---|---|
| Sound power | 83.0 dB(A) |
| Energy class | E |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BC/BD-280MB5-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 65.40 | not rated | not rated | not rated | not rated | not rated |
| 40 | 113.84 | 65.66 | not rated | not rated | not rated | not rated |
| 45 | 161.23 | 113.78 | 65.88 | not rated | not rated | not rated |
| 50 | 208.30 | 160.91 | 113.74 | 66.07 | not rated | not rated |
| 55 | 255.21 | 207.73 | 160.64 | 113.73 | 66.26 | not rated |
| 60 | 302.04 | 254.39 | 207.23 | 160.44 | 113.76 | 66.48 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 52.90 | not rated | not rated | not rated | not rated | not rated |
| 40 | 91.56 | 53.10 | not rated | not rated | not rated | not rated |
| 45 | 129.27 | 91.48 | 53.26 | not rated | not rated | not rated |
| 50 | 166.70 | 128.96 | 91.41 | 53.42 | not rated | not rated |
| 55 | 203.98 | 166.17 | 128.70 | 91.37 | 53.57 | not rated |
| 60 | 241.20 | 203.24 | 165.72 | 128.50 | 91.39 | 53.75 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 113.835 | 19.76 | 48.7 |
| Low speed (Y) | 91.555 | 15.89 | 33.1 |
| A | 5150 mm |
|---|---|
| B | 1450 mm |
| C | 1230 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 4900 mm |
| H | 2400 mm |
| I | 1180 mm |
| K | 5450 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 5450 mm |
|---|---|
| Width | 1230 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.