BC/BD-t-2x180JC1-B03 C
84.02 kW
Defrost: None
Product code: BC/BD-280NC5-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 20,705 m³/h |
|---|---|
| External surface | 557.2 m² |
| Inner volume | 73.9 dm³ |
| Fin material | Aluminium |
| Net weight | 525 kg |
| Quantity | 2 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 35.0 dB(A) |
|---|---|
| Sound power | 67.0 dB(A) |
| Energy class | B |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BC/BD-280NC5-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 50.98 | not rated | not rated | not rated | not rated | not rated |
| 40 | 84.03 | 50.88 | not rated | not rated | not rated | not rated |
| 45 | 116.16 | 83.64 | 50.81 | not rated | not rated | not rated |
| 50 | 147.98 | 115.49 | 83.31 | 50.76 | not rated | not rated |
| 55 | 179.66 | 147.05 | 114.92 | 83.05 | 50.75 | not rated |
| 60 | 211.26 | 178.47 | 146.25 | 114.47 | 82.89 | 50.81 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 40.50 | not rated | not rated | not rated | not rated | not rated |
| 40 | 66.18 | 40.43 | not rated | not rated | not rated | not rated |
| 45 | 91.10 | 65.87 | 40.37 | not rated | not rated | not rated |
| 50 | 115.76 | 90.57 | 65.61 | 40.34 | not rated | not rated |
| 55 | 140.31 | 115.03 | 90.12 | 65.41 | 40.34 | not rated |
| 60 | 164.79 | 139.38 | 114.41 | 89.78 | 65.29 | 40.39 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 84.031 | 14.57 | 45.3 |
| Low speed (Y) | 66.182 | 11.48 | 29.6 |
| A | 5150 mm |
|---|---|
| B | 1450 mm |
| C | 1240 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 4900 mm |
| H | 2400 mm |
| I | 1190 mm |
| K | 5450 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 5450 mm |
|---|---|
| Width | 1240 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.