Dry cooler BC/BD-291BC1-B04 C

Dry cooler BC/BD-291BC1-B04 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-291BC1-B04 C

Heat rejection i
157.19 kW
Air flow
48,790 m³/h
Fans
2 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 48,790 m³/h
External surface 480.5 m²
Inner volume 59.7 dm³
Fin materialAluminium
Net weight 465 kg
Fans
Quantity 2
Diameter 910 mm
Speed 840 rpm
Power 5,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 62.0 dB(A)
Sound power 94.0 dB(A)
Energy class E
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BC/BD-291BC1-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
157.187 kW Fluid flow 27.28 m³/h Pressure drop 93.2 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
122.946 kW Fluid flow 21.34 m³/h Pressure drop 60.2 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 91.58 not rated not rated not rated not rated not rated
40 157.19 91.89 not rated not rated not rated not rated
45 221.28 157.13 92.18 not rated not rated not rated
50 284.87 220.89 157.12 92.47 not rated not rated
55 348.22 284.16 220.61 157.20 92.80 not rated
60 411.44 347.21 283.62 220.48 157.38 93.19

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 72.39 not rated not rated not rated not rated not rated
40 122.95 72.62 not rated not rated not rated not rated
45 172.16 122.88 72.85 not rated not rated not rated
50 220.96 171.82 122.85 73.07 not rated not rated
55 269.55 220.36 171.58 122.88 73.34 not rated
60 318.02 268.71 219.92 171.48 123.05 73.68

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 157.187 27.28 93.2
Low speed (Y) 122.946 21.34 60.2

Dimensions

Dimension drawing of BC/BD-291BC1-B04 C
Dimension drawing
Dimensions as drawn
A 3850 mm
B 1450 mm
C 1240 mm
F 1150 mm
G 550 mm
E 3600 mm
H 1750 mm
I 1190 mm
K 4150 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 4150 mm
Width 1240 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.