BC/BD-463CB5-B19 C
118.89 kW
Defrost: None
Product code: BC/BD-291EB1-B04 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 47,882 m³/h |
|---|---|
| External surface | 288.3 m² |
| Inner volume | 39.8 dm³ |
| Fin material | Aluminium |
| Net weight | 387 kg |
| Quantity | 2 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 5,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 62.0 dB(A) |
|---|---|
| Sound power | 94.0 dB(A) |
| Energy class | E |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BC/BD-291EB1-B04 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 67.31 | not rated | not rated | not rated | not rated | not rated |
| 40 | 118.97 | 67.76 | not rated | not rated | not rated | not rated |
| 45 | 169.67 | 119.21 | 68.17 | not rated | not rated | not rated |
| 50 | 220.06 | 169.72 | 119.46 | 68.55 | not rated | not rated |
| 55 | 270.31 | 219.93 | 169.82 | 119.72 | 68.93 | not rated |
| 60 | 320.47 | 270.00 | 219.89 | 169.98 | 120.04 | 69.33 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 54.60 | not rated | not rated | not rated | not rated | not rated |
| 40 | 95.68 | 54.97 | not rated | not rated | not rated | not rated |
| 45 | 135.87 | 95.86 | 55.30 | not rated | not rated | not rated |
| 50 | 175.77 | 135.90 | 96.05 | 55.61 | not rated | not rated |
| 55 | 215.54 | 175.65 | 135.96 | 96.27 | 55.93 | not rated |
| 60 | 255.23 | 215.28 | 175.61 | 136.10 | 96.54 | 56.27 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 118.973 | 20.65 | 75.1 |
| Low speed (Y) | 95.679 | 16.61 | 51.0 |
| A | 3150 mm |
|---|---|
| B | 1450 mm |
| C | 1240 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 2900 mm |
| H | 1400 mm |
| I | 1190 mm |
| K | 3450 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 3450 mm |
|---|---|
| Width | 1240 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.