Skip to Content

Dry cooler BC/BD-291LB1-B04 C

Dry cooler BC/BD-291LB1-B04 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-291LB1-B04 C

Heat rejection i
125.78 kW
Air flow
51,846 m³/h
Fans
2 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 51,846 m³/h
External surface 271.4 m²
Inner volume 35.7 dm³
Fin materialAluminium
Net weight 403 kg
Fans
Quantity 2
Diameter 910 mm
Speed 840 rpm
Power 5,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 62.0 dB(A)
Sound power 93.5 dB(A)
Energy class E
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BC/BD-291LB1-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
125.780 kW Fluid flow 21.83 m³/h Pressure drop 44.2 kPa
Heat rejection · Low speed (Y)
101.187 kW Fluid flow 17.56 m³/h Pressure drop 30.0 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 70.42 not rated not rated not rated not rated not rated
40 125.78 71.02 not rated not rated not rated not rated
45 179.98 126.08 71.54 not rated not rated not rated
50 233.82 180.03 126.35 72.00 not rated not rated
55 287.50 233.64 180.10 126.63 72.44 not rated
60 341.08 287.10 233.53 180.23 126.95 72.88

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 57.02 not rated not rated not rated not rated not rated
40 101.19 57.52 not rated not rated not rated not rated
45 144.28 101.42 57.95 not rated not rated not rated
50 187.04 144.32 101.65 58.34 not rated not rated
55 229.64 186.89 144.39 101.90 58.73 not rated
60 272.16 229.33 186.82 144.51 102.18 59.12

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 125.780 21.83 44.2
Low speed (Y) 101.187 17.56 30.0

Dimensions

Dimension drawing of BC/BD-291LB1-B04 C
Dimension drawing
Dimensions as drawn
A 3850 mm
B 1450 mm
C 1230 mm
F 1150 mm
G 550 mm
E 3600 mm
H 1750 mm
I 1180 mm
K 4150 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 4150 mm
Width 1230 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.