Skip to Content

Dry cooler BC/BD-291LB5-B04 C

Dry cooler BC/BD-291LB5-B04 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-291LB5-B04 C

Heat rejection i
113.56 kW
Air flow
52,693 m³/h
Fans
2 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 52,693 m³/h
External surface 229.9 m²
Inner volume 35.7 dm³
Fin materialAluminium
Net weight 398 kg
Fans
Quantity 2
Diameter 910 mm
Speed 840 rpm
Power 5,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 61.0 dB(A)
Sound power 93.3 dB(A)
Energy class E
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BC/BD-291LB5-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
113.561 kW Fluid flow 19.71 m³/h Pressure drop 36.8 kPa
Heat rejection · Low speed (Y)
92.384 kW Fluid flow 16.04 m³/h Pressure drop 25.5 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 63.28 not rated not rated not rated not rated not rated
40 113.56 63.85 not rated not rated not rated not rated
45 162.83 113.87 64.34 not rated not rated not rated
50 211.81 162.94 114.15 64.77 not rated not rated
55 260.64 211.73 163.06 114.44 65.18 not rated
60 309.39 260.39 211.70 163.22 114.74 65.59

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 51.74 not rated not rated not rated not rated not rated
40 92.38 52.23 not rated not rated not rated not rated
45 132.07 92.64 52.65 not rated not rated not rated
50 171.48 132.17 92.88 53.03 not rated not rated
55 210.76 171.42 132.27 93.13 53.38 not rated
60 249.96 210.56 171.42 132.43 93.40 53.74

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 113.561 19.71 36.8
Low speed (Y) 92.384 16.04 25.5

Dimensions

Dimension drawing of BC/BD-291LB5-B04 C
Dimension drawing
Dimensions as drawn
A 3850 mm
B 1450 mm
C 1230 mm
F 1150 mm
G 550 mm
E 3600 mm
H 1750 mm
I 1180 mm
K 4150 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 4150 mm
Width 1230 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.