Skip to Content

Dry cooler BC/BD-291MC5-B04 C

Dry cooler BC/BD-291MC5-B04 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-291MC5-B04 C

Heat rejection i
159.52 kW
Air flow
54,403 m³/h
Fans
2 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 54,403 m³/h
External surface 420.4 m²
Inner volume 57.0 dm³
Fin materialAluminium
Net weight 500 kg
Fans
Quantity 2
Diameter 910 mm
Speed 840 rpm
Power 5,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 61.0 dB(A)
Sound power 93.0 dB(A)
Energy class E
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BC/BD-291MC5-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
159.520 kW Fluid flow 27.69 m³/h Pressure drop 56.6 kPa
Heat rejection · Low speed (Y)
127.498 kW Fluid flow 22.13 m³/h Pressure drop 37.9 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 92.17 not rated not rated not rated not rated not rated
40 159.52 92.51 not rated not rated not rated not rated
45 225.32 159.42 92.81 not rated not rated not rated
50 290.62 224.84 159.35 93.09 not rated not rated
55 355.69 289.78 224.44 159.33 93.37 not rated
60 420.64 354.50 289.07 224.16 159.41 93.70

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 74.17 not rated not rated not rated not rated not rated
40 127.50 74.47 not rated not rated not rated not rated
45 179.44 127.42 74.72 not rated not rated not rated
50 230.94 179.06 127.37 74.96 not rated not rated
55 282.25 230.28 178.76 127.39 75.23 not rated
60 333.43 281.30 229.74 178.57 127.49 75.53

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 159.520 27.69 56.6
Low speed (Y) 127.498 22.13 37.9

Dimensions

Dimension drawing of BC/BD-291MC5-B04 C
Dimension drawing
Dimensions as drawn
A 5150 mm
B 1450 mm
C 1230 mm
F 1150 mm
G 550 mm
E 4900 mm
H 2400 mm
I 1180 mm
K 5450 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 5450 mm
Width 1230 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.