BC/BD-263BC5-B01 C
51.25 kW
Defrost: None
Product code: BC/BD-2X163CC5-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 16,685 m³/h |
|---|---|
| External surface | 208.9 m² |
| Inner volume | 32.0 dm³ |
| Fin material | Aluminium |
| Net weight | 250 kg |
| Quantity | 2 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 1,200 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 45.0 dB(A) |
|---|---|
| Sound power | 77.1 dB(A) |
| Energy class | D |
| Inlet | 1 1/2" |
|---|---|
| Outlet | 1 1/2" |
| BC/BD-2X163CC5-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 27.15 | not rated | not rated | not rated | not rated | not rated |
| 40 | 51.27 | 27.76 | not rated | not rated | not rated | not rated |
| 45 | 74.17 | 51.51 | 28.26 | not rated | not rated | not rated |
| 50 | 96.75 | 74.22 | 51.73 | 28.67 | not rated | not rated |
| 55 | 119.19 | 96.64 | 74.28 | 51.93 | 29.04 | not rated |
| 60 | 141.54 | 118.92 | 96.56 | 74.36 | 52.15 | 29.39 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 51.266 | 8.90 | 13.0 |
| A | 1200 mm |
|---|---|
| B | 1200 mm |
| C | 2360 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 1000 mm |
| H | 900 mm |
| I | 2310 mm |
| K | 1500 mm |
| D IN | 1 1/2" |
| D OUT | 1 1/2" |
| Length | 1500 mm |
|---|---|
| Width | 2360 mm |
| Height | 1200 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.