Heat rejection i
69.60 kW
Air flow
21,942 m³/h
Fans
2 × ⌀630 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 21,942 m³/h
External surface 261.0 m²
Inner volume 38.2 dm³
Fin materialAluminium
Net weight 267 kg
Fans
Quantity 2
Diameter 630 mm
Speed 1,330 rpm
Power 2,500 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 54.0 dB(A)
Sound power 86.0 dB(A)
Energy class E
Connections
Inlet 1 1/2"
Outlet 1 1/2"
Defrost
BC/BD-2X163CD5-B19 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
69.601 kW Fluid flow 12.08 m³/h Pressure drop 21.0 kPa
Heat rejection · Low speed (Y)
58.184 kW Fluid flow 10.10 m³/h Pressure drop 15.0 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 37.08 not rated not rated not rated not rated not rated
40 69.60 37.86 not rated not rated not rated not rated
45 100.55 69.90 38.48 not rated not rated not rated
50 131.05 100.57 70.16 39.01 not rated not rated
55 161.35 130.85 100.61 70.40 39.49 not rated
60 191.53 160.93 130.69 100.67 70.67 39.93

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 31.05 not rated not rated not rated not rated not rated
40 58.18 31.77 not rated not rated not rated not rated
45 83.72 58.42 32.33 not rated not rated not rated
50 108.82 83.71 58.64 32.81 not rated not rated
55 133.73 108.62 83.72 58.84 33.24 not rated
60 158.53 133.35 108.47 83.78 59.07 33.63

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 69.601 12.08 21.0
Low speed (Y) 58.184 10.10 15.0

Dimensions

Dimension drawing of BC/BD-2X163CD5-B19 C
Dimension drawing
Dimensions as drawn
A 1200 mm
B 1200 mm
C 2360 mm
F 1050 mm
G 450 mm
E 1000 mm
H 900 mm
I 2310 mm
K 1500 mm
D IN 1 1/2"
D OUT 1 1/2"
Overall [mm]
Length 1500 mm
Width 2360 mm
Height 1200 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.