Skip to Content

Dry cooler BC/BD-2X180HB1-B01 C

Dry cooler BC/BD-2X180HB1-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2X180HB1-B01 C

Heat rejection i
78.26 kW
Air flow
33,564 m³/h
Fans
2 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 33,564 m³/h
External surface 160.7 m²
Inner volume 33.6 dm³
Fin materialAluminium
Net weight 311 kg
Fans
Quantity 2
Diameter 800 mm
Speed 900 rpm
Power 3,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 52.0 dB(A)
Sound power 84.1 dB(A)
Energy class E
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BC/BD-2X180HB1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
78.258 kW Fluid flow 13.58 m³/h Pressure drop 39.5 kPa
Heat rejection · Low speed (Y)
63.050 kW Fluid flow 10.94 m³/h Pressure drop 27.0 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 43.44 not rated not rated not rated not rated not rated
40 78.26 43.92 not rated not rated not rated not rated
45 112.34 78.60 44.34 not rated not rated not rated
50 146.21 112.58 78.90 44.72 not rated not rated
55 179.97 146.35 112.81 79.21 45.08 not rated
60 213.67 180.03 146.51 113.06 79.53 45.44

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 35.21 not rated not rated not rated not rated not rated
40 63.05 35.61 not rated not rated not rated not rated
45 90.20 63.31 35.94 not rated not rated not rated
50 117.13 90.37 63.53 36.24 not rated not rated
55 143.97 117.22 90.50 63.75 36.53 not rated
60 170.75 143.99 117.28 90.67 64.00 36.83

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 78.258 13.58 39.5
Low speed (Y) 63.050 10.94 27.0

Dimensions

Dimension drawing of BC/BD-2X180HB1-B01 C
Dimension drawing
Dimensions as drawn
A 1400 mm
B 1450 mm
C 2310 mm
F 1150 mm
G 550 mm
E 1150 mm
H 1050 mm
I 2260 mm
K 1700 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 1400 mm
Width 2310 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.