BC/BD-2X263BB1-B01 C
96.91 kW
Defrost: None
Product code: BC/BD-2X180HD1-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 28,643 m³/h |
|---|---|
| External surface | 267.9 m² |
| Inner volume | 43.9 dm³ |
| Fin material | Aluminium |
| Net weight | 342 kg |
| Quantity | 2 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 3,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 55.0 dB(A) |
|---|---|
| Sound power | 86.5 dB(A) |
| Energy class | E |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BC/BD-2X180HD1-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 56.41 | not rated | not rated | not rated | not rated | not rated |
| 40 | 97.10 | 56.78 | not rated | not rated | not rated | not rated |
| 45 | 136.67 | 97.27 | 57.13 | not rated | not rated | not rated |
| 50 | 175.89 | 136.69 | 97.47 | 57.47 | not rated | not rated |
| 55 | 214.92 | 175.75 | 136.78 | 97.72 | 57.83 | not rated |
| 60 | 253.87 | 214.67 | 175.74 | 136.96 | 98.06 | 58.24 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 43.60 | not rated | not rated | not rated | not rated | not rated |
| 40 | 74.33 | 43.90 | not rated | not rated | not rated | not rated |
| 45 | 104.10 | 74.45 | 44.17 | not rated | not rated | not rated |
| 50 | 133.55 | 104.10 | 74.60 | 44.45 | not rated | not rated |
| 55 | 162.87 | 133.45 | 104.17 | 74.81 | 44.74 | not rated |
| 60 | 192.10 | 162.66 | 133.45 | 104.34 | 75.09 | 45.08 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 97.096 | 16.85 | 53.0 |
| Low speed (Y) | 74.334 | 12.90 | 33.0 |
| A | 1400 mm |
|---|---|
| B | 1450 mm |
| C | 2310 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 1150 mm |
| H | 1050 mm |
| I | 2260 mm |
| K | 1700 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 1400 mm |
|---|---|
| Width | 2310 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.