BC/BD-480CC5-B01I C
232.22 kW
Defrost: None
Product code: BC/BD-2X280CC5-B01I C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 71,393 m³/h |
|---|---|
| External surface | 812.5 m² |
| Inner volume | 141.8 dm³ |
| Fin material | Aluminium |
| Net weight | 793 kg |
| Quantity | 4 |
|---|---|
| Diameter | 800 mm |
| Speed | 880 rpm |
| Power | 7,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 55.0 dB(A) |
|---|---|
| Sound power | 86.8 dB(A) |
| Energy class | E |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BC/BD-2X280CC5-B01I C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 135.67 | not rated | not rated | not rated | not rated | not rated |
| 40 | 232.35 | 136.01 | not rated | not rated | not rated | not rated |
| 45 | 326.72 | 232.03 | 136.31 | not rated | not rated | not rated |
| 50 | 420.33 | 325.82 | 231.77 | 136.61 | not rated | not rated |
| 55 | 513.60 | 418.86 | 325.05 | 231.64 | 136.95 | not rated |
| 60 | 606.66 | 511.57 | 417.61 | 324.52 | 231.66 | 137.37 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 232.351 | 40.33 | 53.6 |
| A | 3850 mm |
|---|---|
| B | 1450 mm |
| C | 2360 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 3600 mm |
| H | 1750 mm |
| I | 2310 mm |
| K | 4150 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 3850 mm |
|---|---|
| Width | 2360 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.