Skip to Content

Dry cooler BC/BD-2X280HC5-B01 C

Dry cooler BC/BD-2X280HC5-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2X280HC5-B01 C

Heat rejection i
168.01 kW
Air flow
63,762 m³/h
Fans
4 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 63,762 m³/h
External surface 363.1 m²
Inner volume 65.6 dm³
Fin materialAluminium
Net weight 572 kg
Fans
Quantity 4
Diameter 800 mm
Speed 900 rpm
Power 7,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 56.0 dB(A)
Sound power 87.9 dB(A)
Energy class E
Connections
Inlet 3"
Outlet 3"
Defrost
BC/BD-2X280HC5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
168.006 kW Fluid flow 29.16 m³/h Pressure drop 55.6 kPa
Heat rejection · Low speed (Y)
133.496 kW Fluid flow 23.17 m³/h Pressure drop 37.0 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 95.76 not rated not rated not rated not rated not rated
40 168.01 96.50 not rated not rated not rated not rated
45 238.70 168.47 97.16 not rated not rated not rated
50 308.90 238.96 168.95 97.80 not rated not rated
55 378.87 308.98 239.29 169.48 98.43 not rated
60 448.72 378.79 309.19 239.75 170.08 99.09

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 76.62 not rated not rated not rated not rated not rated
40 133.50 77.21 not rated not rated not rated not rated
45 188.96 133.85 77.76 not rated not rated not rated
50 243.99 189.15 134.23 78.28 not rated not rated
55 298.81 244.03 189.41 134.65 78.81 not rated
60 353.52 298.71 244.19 189.78 135.17 79.38

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 168.006 29.16 55.6
Low speed (Y) 133.496 23.17 37.0

Dimensions

Dimension drawing of BC/BD-2X280HC5-B01 C
Dimension drawing
Dimensions as drawn
A 2450 mm
B 1450 mm
C 2310 mm
F 1150 mm
G 550 mm
E 2200 mm
H 1050 mm
I 2260 mm
K 2750 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 2450 mm
Width 2310 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.