BC/BD-380KD1-B03 C
114.74 kW
Defrost: None
Product code: BC/BD-2X350CC1-B09 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 36,561 m³/h |
|---|---|
| External surface | 382.4 m² |
| Inner volume | 58.0 dm³ |
| Fin material | Aluminium |
| Net weight | 401 kg |
| Quantity | 6 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,330 rpm |
| Power | 4,300 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 54.0 dB(A) |
|---|---|
| Sound power | 86.0 dB(A) |
| Energy class | E |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BC/BD-2X350CC1-B09 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 64.20 | not rated | not rated | not rated | not rated | not rated |
| 40 | 114.71 | 64.89 | not rated | not rated | not rated | not rated |
| 45 | 163.76 | 115.03 | 65.48 | not rated | not rated | not rated |
| 50 | 212.32 | 163.80 | 115.35 | 66.02 | not rated | not rated |
| 55 | 260.66 | 212.12 | 163.90 | 115.69 | 66.56 | not rated |
| 60 | 308.87 | 260.23 | 212.02 | 164.09 | 116.09 | 67.10 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 114.713 | 19.91 | 17.7 |
| A | 2250 mm |
|---|---|
| B | 1200 mm |
| C | 1720 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 2050 mm |
| H | 650 mm |
| I | 1670 mm |
| K | 2550 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 2550 mm |
|---|---|
| Width | 1720 mm |
| Height | 1200 mm |