BC/BD-380KC5-B03 C
103.81 kW
Defrost: None
Product code: BC/BD-2X363BA5-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 55,385 m³/h |
|---|---|
| External surface | 233.4 m² |
| Inner volume | 50.9 dm³ |
| Fin material | Aluminium |
| Net weight | 448 kg |
| Quantity | 6 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 3,600 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 51.0 dB(A) |
|---|---|
| Sound power | 82.7 dB(A) |
| Energy class | E |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BC/BD-2X363BA5-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 58.24 | not rated | not rated | not rated | not rated | not rated |
| 40 | 103.83 | 58.68 | not rated | not rated | not rated | not rated |
| 45 | 148.59 | 104.06 | 59.05 | not rated | not rated | not rated |
| 50 | 193.11 | 148.66 | 104.27 | 59.37 | not rated | not rated |
| 55 | 237.52 | 193.03 | 148.74 | 104.47 | 59.68 | not rated |
| 60 | 281.86 | 237.30 | 192.98 | 148.84 | 104.69 | 59.98 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 103.832 | 18.02 | 43.3 |
| A | 3050 mm |
|---|---|
| B | 1220 mm |
| C | 2310 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 2800 mm |
| H | 900 mm |
| I | 2260 mm |
| K | 3300 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 3050 mm |
|---|---|
| Width | 2310 mm |
| Height | 1220 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.