Skip to Content

Dry cooler BC/BD-2X363BD5-B19 C

Dry cooler BC/BD-2X363BD5-B19 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2X363BD5-B19 C

Heat rejection i
215.26 kW
Air flow
66,123 m³/h
Fans
6 × ⌀630 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 66,123 m³/h
External surface 583.6 m²
Inner volume 107.6 dm³
Fin materialAluminium
Net weight 554 kg
Fans
Quantity 6
Diameter 630 mm
Speed 1,330 rpm
Power 7,500 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 59.0 dB(A)
Sound power 91.0 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-2X363BD5-B19 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
215.261 kW Fluid flow 37.36 m³/h Pressure drop 68.8 kPa
Heat rejection · Low speed (Y)
179.339 kW Fluid flow 31.12 m³/h Pressure drop 49.9 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 126.09 not rated not rated not rated not rated not rated
40 215.26 126.43 not rated not rated not rated not rated
45 302.27 215.03 126.74 not rated not rated not rated
50 388.58 301.54 214.85 127.04 not rated not rated
55 474.56 387.37 300.94 214.80 127.39 not rated
60 560.37 472.89 386.37 300.55 214.90 127.82

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 105.70 not rated not rated not rated not rated not rated
40 179.34 105.99 not rated not rated not rated not rated
45 251.05 179.14 106.25 not rated not rated not rated
50 322.10 250.42 178.99 106.52 not rated not rated
55 392.88 321.07 249.90 178.95 106.84 not rated
60 463.50 391.46 320.24 249.60 179.07 107.24

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 215.261 37.36 68.8
Low speed (Y) 179.339 31.12 49.9

Dimensions

Dimension drawing of BC/BD-2X363BD5-B19 C
Dimension drawing
Dimensions as drawn
A 3150 mm
B 1220 mm
C 2310 mm
F 1050 mm
G 450 mm
E 2800 mm
H 900 mm
I 2260 mm
K 3500 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 3150 mm
Width 2310 mm
Height 1220 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.