BC/BD-t-2X463AB5-B01 C
215.45 kW
Defrost: None
Product code: BC/BD-2X363BD5-B19 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 66,123 m³/h |
|---|---|
| External surface | 583.6 m² |
| Inner volume | 107.6 dm³ |
| Fin material | Aluminium |
| Net weight | 554 kg |
| Quantity | 6 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 7,500 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 91.0 dB(A) |
| Energy class | E |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BC/BD-2X363BD5-B19 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 126.09 | not rated | not rated | not rated | not rated | not rated |
| 40 | 215.26 | 126.43 | not rated | not rated | not rated | not rated |
| 45 | 302.27 | 215.03 | 126.74 | not rated | not rated | not rated |
| 50 | 388.58 | 301.54 | 214.85 | 127.04 | not rated | not rated |
| 55 | 474.56 | 387.37 | 300.94 | 214.80 | 127.39 | not rated |
| 60 | 560.37 | 472.89 | 386.37 | 300.55 | 214.90 | 127.82 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 105.70 | not rated | not rated | not rated | not rated | not rated |
| 40 | 179.34 | 105.99 | not rated | not rated | not rated | not rated |
| 45 | 251.05 | 179.14 | 106.25 | not rated | not rated | not rated |
| 50 | 322.10 | 250.42 | 178.99 | 106.52 | not rated | not rated |
| 55 | 392.88 | 321.07 | 249.90 | 178.95 | 106.84 | not rated |
| 60 | 463.50 | 391.46 | 320.24 | 249.60 | 179.07 | 107.24 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 215.261 | 37.36 | 68.8 |
| Low speed (Y) | 179.339 | 31.12 | 49.9 |
| A | 3150 mm |
|---|---|
| B | 1220 mm |
| C | 2310 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 2800 mm |
| H | 900 mm |
| I | 2260 mm |
| K | 3500 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 3150 mm |
|---|---|
| Width | 2310 mm |
| Height | 1220 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.