BC/BD-2X563CB5-B01 C
237.63 kW
Defrost: None
Product code: BC/BD-2X363CD1-B19 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 64,559 m³/h |
|---|---|
| External surface | 926.6 m² |
| Inner volume | 120.8 dm³ |
| Fin material | Aluminium |
| Net weight | 671 kg |
| Quantity | 6 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 7,500 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 91.0 dB(A) |
| Energy class | E |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BC/BD-2X363CD1-B19 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 138.61 | not rated | not rated | not rated | not rated | not rated |
| 40 | 237.61 | 139.18 | not rated | not rated | not rated | not rated |
| 45 | 333.58 | 237.33 | 139.69 | not rated | not rated | not rated |
| 50 | 428.57 | 332.63 | 237.15 | 140.18 | not rated | not rated |
| 55 | 523.10 | 426.97 | 331.88 | 237.12 | 140.73 | not rated |
| 60 | 617.35 | 520.87 | 425.67 | 331.39 | 237.30 | 141.37 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 114.80 | not rated | not rated | not rated | not rated | not rated |
| 40 | 195.03 | 115.39 | not rated | not rated | not rated | not rated |
| 45 | 272.59 | 195.02 | 115.93 | not rated | not rated | not rated |
| 50 | 349.26 | 272.10 | 195.06 | 116.46 | not rated | not rated |
| 55 | 425.49 | 348.32 | 271.76 | 195.23 | 117.00 | not rated |
| 60 | 501.50 | 424.14 | 347.63 | 271.65 | 195.59 | 117.57 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 237.611 | 41.24 | 38.2 |
| Low speed (Y) | 195.033 | 33.83 | 26.7 |
| A | 3000 mm |
|---|---|
| B | 1200 mm |
| C | 2360 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 2800 mm |
| H | 900 mm |
| I | 2310 mm |
| K | 3300 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 3300 mm |
|---|---|
| Width | 2360 mm |
| Height | 1200 mm |
Our engineers answer with a selection for your conditions.