BC/BD-t-291PC1-B04 C
176.78 kW
Defrost: None
Product code: BC/BD-2X363CD5-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 47,816 m³/h |
|---|---|
| External surface | 783.5 m² |
| Inner volume | 120.8 dm³ |
| Fin material | Aluminium |
| Net weight | 649 kg |
| Quantity | 6 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 3,600 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 50.0 dB(A) |
|---|---|
| Sound power | 82.4 dB(A) |
| Energy class | D |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BC/BD-2X363CD5-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 103.25 | not rated | not rated | not rated | not rated | not rated |
| 40 | 176.75 | 103.76 | not rated | not rated | not rated | not rated |
| 45 | 247.95 | 176.67 | 104.21 | not rated | not rated | not rated |
| 50 | 318.39 | 247.38 | 176.63 | 104.64 | not rated | not rated |
| 55 | 388.46 | 317.37 | 246.96 | 176.70 | 105.12 | not rated |
| 60 | 458.34 | 387.02 | 316.58 | 246.74 | 176.94 | 105.67 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 176.751 | 30.65 | 22.4 |
| A | 3000 mm |
|---|---|
| B | 1200 mm |
| C | 2360 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 2800 mm |
| H | 900 mm |
| I | 2310 mm |
| K | 3300 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 3300 mm |
|---|---|
| Width | 2360 mm |
| Height | 1200 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.