BC/BD-663BC1-B19 C
212.49 kW
Defrost: None
Product code: BC/BD-2X380HB5-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 103,431 m³/h |
|---|---|
| External surface | 408.5 m² |
| Inner volume | 87.8 dm³ |
| Fin material | Aluminium |
| Net weight | 780 kg |
| Quantity | 6 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 10,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 57.0 dB(A) |
|---|---|
| Sound power | 89.0 dB(A) |
| Energy class | E |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BC/BD-2X380HB5-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 117.08 | not rated | not rated | not rated | not rated | not rated |
| 40 | 212.41 | 118.44 | not rated | not rated | not rated | not rated |
| 45 | 305.78 | 213.37 | 119.65 | not rated | not rated | not rated |
| 50 | 398.60 | 306.46 | 214.26 | 120.73 | not rated | not rated |
| 55 | 491.15 | 399.04 | 307.15 | 215.14 | 121.74 | not rated |
| 60 | 583.56 | 491.37 | 399.55 | 307.90 | 216.05 | 122.72 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 95.60 | not rated | not rated | not rated | not rated | not rated |
| 40 | 172.61 | 96.74 | not rated | not rated | not rated | not rated |
| 45 | 247.75 | 173.32 | 97.71 | not rated | not rated | not rated |
| 50 | 322.35 | 248.21 | 174.00 | 98.59 | not rated | not rated |
| 55 | 396.71 | 322.57 | 248.67 | 174.67 | 99.43 | not rated |
| 60 | 470.93 | 396.72 | 322.85 | 249.20 | 175.37 | 100.24 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 212.406 | 36.87 | 29.1 |
| Low speed (Y) | 172.607 | 29.96 | 20.2 |
| A | 3500 mm |
|---|---|
| B | 1450 mm |
| C | 2310 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 3250 mm |
| H | 1050 mm |
| I | 2260 mm |
| K | 3800 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 3500 mm |
|---|---|
| Width | 2310 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.