207.41 kW
Defrost: None
Product code: BC/BD-2X480HA5-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 151,080 m³/h |
|---|---|
| External surface | 363.1 m² |
| Inner volume | 82.7 dm³ |
| Fin material | Aluminium |
| Net weight | 963 kg |
| Quantity | 8 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 14,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 57.0 dB(A) |
|---|---|
| Sound power | 89.2 dB(A) |
| Energy class | E |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BC/BD-2X480HA5-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 107.06 | not rated | not rated | not rated | not rated | not rated |
| 40 | 207.38 | 109.49 | not rated | not rated | not rated | not rated |
| 45 | 305.25 | 209.14 | 111.56 | not rated | not rated | not rated |
| 50 | 402.61 | 306.73 | 210.72 | 113.34 | not rated | not rated |
| 55 | 499.75 | 403.83 | 308.07 | 212.17 | 114.91 | not rated |
| 60 | 596.75 | 500.76 | 405.00 | 309.37 | 213.52 | 116.32 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 88.64 | not rated | not rated | not rated | not rated | not rated |
| 40 | 171.70 | 90.78 | not rated | not rated | not rated | not rated |
| 45 | 252.22 | 173.12 | 92.57 | not rated | not rated | not rated |
| 50 | 332.17 | 253.32 | 174.40 | 94.10 | not rated | not rated |
| 55 | 411.87 | 333.03 | 254.35 | 175.56 | 95.45 | not rated |
| 60 | 491.44 | 412.53 | 333.88 | 255.34 | 176.65 | 96.67 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 207.375 | 35.99 | 12.3 |
| Low speed (Y) | 171.699 | 29.80 | 8.8 |
| A | 4550 mm |
|---|---|
| B | 1450 mm |
| C | 2310 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 4300 mm |
| H | 1050 mm |
| I | 2260 mm |
| K | 4850 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 4550 mm |
|---|---|
| Width | 2310 mm |
| Height | 1450 mm |