Skip to Content

Dry cooler BC/BD-2X480HC1-B01 C

Dry cooler BC/BD-2X480HC1-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2X480HC1-B01 C

Heat rejection i
362.59 kW
Air flow
123,351 m³/h
Fans
8 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 123,351 m³/h
External surface 857.3 m²
Inner volume 145.6 dm³
Fin materialAluminium
Net weight 1,088 kg
Fans
Quantity 8
Diameter 800 mm
Speed 900 rpm
Power 14,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 59.0 dB(A)
Sound power 91.4 dB(A)
Energy class E
Connections
Inlet 5"
Outlet 5"
Defrost
BC/BD-2X480HC1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
362.589 kW Fluid flow 62.93 m³/h Pressure drop 57.0 kPa
Heat rejection · Low speed (Y)
284.525 kW Fluid flow 49.38 m³/h Pressure drop 37.1 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 207.84 not rated not rated not rated not rated not rated
40 362.59 209.36 not rated not rated not rated not rated
45 513.73 363.49 210.75 not rated not rated not rated
50 663.71 514.13 364.43 212.10 not rated not rated
55 813.15 663.67 514.73 365.51 213.49 not rated
60 962.29 812.69 663.95 515.64 366.84 214.95

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 164.45 not rated not rated not rated not rated not rated
40 284.53 165.66 not rated not rated not rated not rated
45 401.39 285.18 166.76 not rated not rated not rated
50 517.22 401.65 285.88 167.84 not rated not rated
55 632.58 517.12 402.05 286.74 168.97 not rated
60 747.67 632.13 517.26 402.76 287.80 170.19

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 362.589 62.93 57.0
Low speed (Y) 284.525 49.38 37.1

Dimensions

Dimension drawing of BC/BD-2X480HC1-B01 C
Dimension drawing
Dimensions as drawn
A 4750 mm
B 1450 mm
C 2310 mm
F 1150 mm
G 550 mm
E 4300 mm
H 1050 mm
I 2260 mm
K 5250 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 4750 mm
Width 2310 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.