Skip to Content

Dry cooler BC/BD-2X480HC5-B01 C

Dry cooler BC/BD-2X480HC5-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2X480HC5-B01 C

Heat rejection i
335.74 kW
Air flow
127,524 m³/h
Fans
8 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 127,524 m³/h
External surface 726.2 m²
Inner volume 145.6 dm³
Fin materialAluminium
Net weight 1,071 kg
Fans
Quantity 8
Diameter 800 mm
Speed 900 rpm
Power 14,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 59.0 dB(A)
Sound power 90.9 dB(A)
Energy class E
Connections
Inlet 5"
Outlet 5"
Defrost
BC/BD-2X480HC5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
335.737 kW Fluid flow 58.27 m³/h Pressure drop 49.7 kPa
Heat rejection · Low speed (Y)
266.786 kW Fluid flow 46.30 m³/h Pressure drop 33.1 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 191.24 not rated not rated not rated not rated not rated
40 335.74 192.72 not rated not rated not rated not rated
45 477.12 336.69 194.06 not rated not rated not rated
50 617.53 477.67 337.65 195.35 not rated not rated
55 757.48 617.71 478.34 338.70 196.62 not rated
60 897.18 757.32 618.13 479.26 339.93 197.96

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 153.02 not rated not rated not rated not rated not rated
40 266.79 154.22 not rated not rated not rated not rated
45 377.73 267.51 155.32 not rated not rated not rated
50 487.79 378.11 268.27 156.37 not rated not rated
55 597.43 487.87 378.63 269.13 157.44 not rated
60 706.85 597.23 488.19 379.39 270.17 158.58

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 335.737 58.27 49.7
Low speed (Y) 266.786 46.30 33.1

Dimensions

Dimension drawing of BC/BD-2X480HC5-B01 C
Dimension drawing
Dimensions as drawn
A 4750 mm
B 1450 mm
C 2310 mm
F 1150 mm
G 550 mm
E 4300 mm
H 1050 mm
I 2260 mm
K 5250 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 4750 mm
Width 2310 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.