BC/BD-t-2X563AB5-B19 C
335.76 kW
Defrost: None
Product code: BC/BD-2X480HC5-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 127,524 m³/h |
|---|---|
| External surface | 726.2 m² |
| Inner volume | 145.6 dm³ |
| Fin material | Aluminium |
| Net weight | 1,071 kg |
| Quantity | 8 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 14,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 90.9 dB(A) |
| Energy class | E |
| Inlet | 5" |
|---|---|
| Outlet | 5" |
| BC/BD-2X480HC5-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 191.24 | not rated | not rated | not rated | not rated | not rated |
| 40 | 335.74 | 192.72 | not rated | not rated | not rated | not rated |
| 45 | 477.12 | 336.69 | 194.06 | not rated | not rated | not rated |
| 50 | 617.53 | 477.67 | 337.65 | 195.35 | not rated | not rated |
| 55 | 757.48 | 617.71 | 478.34 | 338.70 | 196.62 | not rated |
| 60 | 897.18 | 757.32 | 618.13 | 479.26 | 339.93 | 197.96 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 153.02 | not rated | not rated | not rated | not rated | not rated |
| 40 | 266.79 | 154.22 | not rated | not rated | not rated | not rated |
| 45 | 377.73 | 267.51 | 155.32 | not rated | not rated | not rated |
| 50 | 487.79 | 378.11 | 268.27 | 156.37 | not rated | not rated |
| 55 | 597.43 | 487.87 | 378.63 | 269.13 | 157.44 | not rated |
| 60 | 706.85 | 597.23 | 488.19 | 379.39 | 270.17 | 158.58 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 335.737 | 58.27 | 49.7 |
| Low speed (Y) | 266.786 | 46.30 | 33.1 |
| A | 4750 mm |
|---|---|
| B | 1450 mm |
| C | 2310 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 4300 mm |
| H | 1050 mm |
| I | 2260 mm |
| K | 5250 mm |
| D IN | 5" |
| D OUT | 5" |
| Length | 4750 mm |
|---|---|
| Width | 2310 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.