BC/BD-t-2X563AC5-B19 C
387.48 kW
Defrost: None
Product code: BC/BD-2X480HD1-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 114,571 m³/h |
|---|---|
| External surface | 1,071.6 m² |
| Inner volume | 166.1 dm³ |
| Fin material | Aluminium |
| Net weight | 1,148 kg |
| Quantity | 8 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 14,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 60.0 dB(A) |
|---|---|
| Sound power | 92.5 dB(A) |
| Energy class | E |
| Inlet | 5" |
|---|---|
| Outlet | 5" |
| BC/BD-2X480HD1-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 224.81 | not rated | not rated | not rated | not rated | not rated |
| 40 | 387.61 | 226.35 | not rated | not rated | not rated | not rated |
| 45 | 545.95 | 388.36 | 227.79 | not rated | not rated | not rated |
| 50 | 702.83 | 546.07 | 389.18 | 229.19 | not rated | not rated |
| 55 | 858.99 | 702.35 | 546.45 | 390.24 | 230.66 | not rated |
| 60 | 1014.82 | 858.02 | 702.34 | 547.20 | 391.61 | 232.30 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 173.78 | not rated | not rated | not rated | not rated | not rated |
| 40 | 296.80 | 175.02 | not rated | not rated | not rated | not rated |
| 45 | 415.88 | 297.28 | 176.15 | not rated | not rated | not rated |
| 50 | 533.74 | 415.92 | 297.92 | 177.29 | not rated | not rated |
| 55 | 651.01 | 533.34 | 416.22 | 298.78 | 178.50 | not rated |
| 60 | 767.96 | 650.21 | 533.36 | 416.91 | 299.94 | 179.87 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 387.613 | 67.27 | 44.5 |
| Low speed (Y) | 296.802 | 51.51 | 27.7 |
| A | 4750 mm |
|---|---|
| B | 1450 mm |
| C | 2310 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 4300 mm |
| H | 1050 mm |
| I | 2260 mm |
| K | 5250 mm |
| D IN | 5" |
| D OUT | 5" |
| Length | 4750 mm |
|---|---|
| Width | 2310 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.