BC/BD-291MB1-B04 C
150.04 kW
Defrost: None
Product code: BC/BD-2X550DA1-B09 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 73,077 m³/h |
|---|---|
| External surface | 392.2 m² |
| Inner volume | 71.9 dm³ |
| Fin material | Aluminium |
| Net weight | 585 kg |
| Quantity | 10 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,330 rpm |
| Power | 7,100 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 57.0 dB(A) |
|---|---|
| Sound power | 89.0 dB(A) |
| Energy class | E |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BC/BD-2X550DA1-B09 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 82.06 | not rated | not rated | not rated | not rated | not rated |
| 40 | 150.14 | 82.94 | not rated | not rated | not rated | not rated |
| 45 | 216.98 | 150.66 | 83.71 | not rated | not rated | not rated |
| 50 | 283.46 | 217.19 | 151.12 | 84.39 | not rated | not rated |
| 55 | 349.77 | 283.39 | 217.40 | 151.55 | 85.01 | not rated |
| 60 | 415.98 | 349.43 | 283.36 | 217.63 | 152.00 | 85.60 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 150.136 | 26.06 | 24.8 |
| A | 4300 mm |
|---|---|
| B | 1200 mm |
| C | 1720 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 4100 mm |
| H | 800 mm |
| I | 1670 mm |
| K | 4600 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 4600 mm |
|---|---|
| Width | 1720 mm |
| Height | 1200 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.