Dry cooler BC/BD-2X563CA5-B19 C

Dry cooler BC/BD-2X563CA5-B19 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2X563CA5-B19 C

Heat rejection i
219.20 kW
Air flow
122,176 m³/h
Fans
10 × ⌀630 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 122,176 m³/h
External surface 522.3 m²
Inner volume 106.3 dm³
Fin materialAluminium
Net weight 787 kg
Fans
Quantity 10
Diameter 630 mm
Speed 1,330 rpm
Power 12,500 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 62.0 dB(A)
Sound power 94.0 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-2X563CA5-B19 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
219.197 kW Fluid flow 38.04 m³/h Pressure drop 31.3 kPa
Heat rejection · Low speed (Y)
193.430 kW Fluid flow 33.57 m³/h Pressure drop 25.1 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 120.63 not rated not rated not rated not rated not rated
40 219.20 121.75 not rated not rated not rated not rated
45 316.17 219.84 122.70 not rated not rated not rated
50 412.67 316.42 220.40 123.54 not rated not rated
55 508.97 412.53 316.64 220.94 124.31 not rated
60 605.13 508.47 412.43 316.89 221.47 125.05

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 106.84 not rated not rated not rated not rated not rated
40 193.43 107.84 not rated not rated not rated not rated
45 278.45 193.99 108.69 not rated not rated not rated
50 363.00 278.65 194.49 109.46 not rated not rated
55 447.37 362.88 278.85 194.96 110.16 not rated
60 531.59 446.91 362.80 279.08 195.46 110.83

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 219.197 38.04 31.3
Low speed (Y) 193.430 33.57 25.1

Dimensions

Dimension drawing of BC/BD-2X563CA5-B19 C
Dimension drawing
Dimensions as drawn
A 4800 mm
B 1200 mm
C 2360 mm
F 1050 mm
G 450 mm
E 4600 mm
H 900 mm
I 2310 mm
K 5100 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 5100 mm
Width 2360 mm
Height 1200 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.