BC/BD-580FC5-B01 C
315.35 kW
Defrost: None
Product code: BC/BD-2X563CB1-B19 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 116,314 m³/h |
|---|---|
| External surface | 926.6 m² |
| Inner volume | 138.3 dm³ |
| Fin material | Aluminium |
| Net weight | 891 kg |
| Quantity | 10 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 12,500 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 93.0 dB(A) |
| Energy class | E |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BC/BD-2X563CB1-B19 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 176.65 | not rated | not rated | not rated | not rated | not rated |
| 40 | 315.50 | 178.07 | not rated | not rated | not rated | not rated |
| 45 | 451.23 | 315.99 | 179.27 | not rated | not rated | not rated |
| 50 | 585.98 | 450.94 | 316.41 | 180.34 | not rated | not rated |
| 55 | 720.25 | 584.94 | 450.71 | 316.88 | 181.37 | not rated |
| 60 | 854.27 | 718.53 | 584.06 | 450.62 | 317.45 | 182.40 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 152.18 | not rated | not rated | not rated | not rated | not rated |
| 40 | 270.11 | 153.34 | not rated | not rated | not rated | not rated |
| 45 | 385.06 | 270.44 | 154.37 | not rated | not rated | not rated |
| 50 | 499.07 | 384.68 | 270.75 | 155.29 | not rated | not rated |
| 55 | 612.62 | 498.03 | 384.40 | 271.11 | 156.17 | not rated |
| 60 | 725.94 | 610.94 | 497.18 | 384.31 | 271.60 | 157.09 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 315.502 | 54.76 | 32.3 |
| Low speed (Y) | 270.112 | 46.88 | 24.5 |
| A | 4800 mm |
|---|---|
| B | 1200 mm |
| C | 2360 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 4600 mm |
| H | 900 mm |
| I | 2310 mm |
| K | 5100 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 5100 mm |
|---|---|
| Width | 2360 mm |
| Height | 1200 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.