BC/BD-t-2x680GB1-B03 C
361.28 kW
Defrost: None
Product code: BC/BD-2X563CC1-B19 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 111,740 m³/h |
|---|---|
| External surface | 1,235.5 m² |
| Inner volume | 170.2 dm³ |
| Fin material | Aluminium |
| Net weight | 980 kg |
| Quantity | 10 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 12,500 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 93.0 dB(A) |
| Energy class | E |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BC/BD-2X563CC1-B19 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 204.93 | not rated | not rated | not rated | not rated | not rated |
| 40 | 361.09 | 206.38 | not rated | not rated | not rated | not rated |
| 45 | 512.87 | 361.28 | 207.64 | not rated | not rated | not rated |
| 50 | 663.23 | 512.03 | 361.48 | 208.78 | not rated | not rated |
| 55 | 812.94 | 661.41 | 511.35 | 361.79 | 209.90 | not rated |
| 60 | 962.24 | 810.17 | 659.91 | 510.98 | 362.35 | 211.09 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 173.42 | not rated | not rated | not rated | not rated | not rated |
| 40 | 303.31 | 174.65 | not rated | not rated | not rated | not rated |
| 45 | 429.10 | 303.40 | 175.72 | not rated | not rated | not rated |
| 50 | 553.51 | 428.25 | 303.54 | 176.69 | not rated | not rated |
| 55 | 677.34 | 551.88 | 427.63 | 303.79 | 177.64 | not rated |
| 60 | 800.81 | 674.90 | 550.56 | 427.31 | 304.20 | 178.68 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 361.094 | 62.68 | 27.9 |
| Low speed (Y) | 303.310 | 52.64 | 20.4 |
| A | 4800 mm |
|---|---|
| B | 1200 mm |
| C | 2360 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 4600 mm |
| H | 900 mm |
| I | 2310 mm |
| K | 5100 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 5100 mm |
|---|---|
| Width | 2360 mm |
| Height | 1200 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.