BC/BD-2x480AB5-B01 C
334.09 kW
Defrost: None
Product code: BC/BD-2X563CC5-B19 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 113,534 m³/h |
|---|---|
| External surface | 1,044.7 m² |
| Inner volume | 170.2 dm³ |
| Fin material | Aluminium |
| Net weight | 949 kg |
| Quantity | 10 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 12,500 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 93.0 dB(A) |
| Energy class | E |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BC/BD-2X563CC5-B19 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 188.28 | not rated | not rated | not rated | not rated | not rated |
| 40 | 334.15 | 189.74 | not rated | not rated | not rated | not rated |
| 45 | 476.27 | 334.54 | 191.02 | not rated | not rated | not rated |
| 50 | 617.20 | 475.78 | 334.92 | 192.15 | not rated | not rated |
| 55 | 757.57 | 615.89 | 475.41 | 335.35 | 193.25 | not rated |
| 60 | 897.65 | 755.47 | 614.83 | 475.29 | 335.95 | 194.37 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 160.74 | not rated | not rated | not rated | not rated | not rated |
| 40 | 283.49 | 161.99 | not rated | not rated | not rated | not rated |
| 45 | 402.69 | 283.75 | 163.06 | not rated | not rated | not rated |
| 50 | 520.74 | 402.13 | 283.99 | 164.02 | not rated | not rated |
| 55 | 638.26 | 519.45 | 401.73 | 284.31 | 164.98 | not rated |
| 60 | 755.49 | 636.28 | 518.44 | 401.54 | 284.81 | 165.96 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 334.149 | 58.00 | 24.2 |
| Low speed (Y) | 283.490 | 49.20 | 18.0 |
| A | 4800 mm |
|---|---|
| B | 1200 mm |
| C | 2360 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 4600 mm |
| H | 900 mm |
| I | 2310 mm |
| K | 5100 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 5100 mm |
|---|---|
| Width | 2360 mm |
| Height | 1200 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.