BC/BD-980DC1-B01I C
471.32 kW
Defrost: None
Product code: BC/BD-2X580AC5-B01I C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 159,534 m³/h |
|---|---|
| External surface | 1,392.9 m² |
| Inner volume | 235.1 dm³ |
| Fin material | Aluminium |
| Net weight | 1,519 kg |
| Quantity | 10 |
|---|---|
| Diameter | 800 mm |
| Speed | 880 rpm |
| Power | 19,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 93.0 dB(A) |
| Energy class | E |
| Inlet | 5" |
|---|---|
| Outlet | 5" |
| BC/BD-2X580AC5-B01I C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 271.11 | not rated | not rated | not rated | not rated | not rated |
| 40 | 471.87 | 272.62 | not rated | not rated | not rated | not rated |
| 45 | 668.09 | 472.35 | 273.96 | not rated | not rated | not rated |
| 50 | 862.86 | 667.68 | 472.87 | 275.25 | not rated | not rated |
| 55 | 1056.93 | 861.61 | 667.49 | 473.56 | 276.59 | not rated |
| 60 | 1250.61 | 1054.87 | 860.75 | 667.70 | 474.56 | 278.03 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 471.871 | 81.90 | 48.1 |
| A | 6350 mm |
|---|---|
| B | 1450 mm |
| C | 2360 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 6100 mm |
| H | 1200 mm |
| I | 2310 mm |
| K | 6750 mm |
| D IN | 5" |
| D OUT | 5" |
| Length | 6350 mm |
|---|---|
| Width | 2360 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.