Skip to Content

Dry cooler BC/BD-2X580CC1-B01 C

Dry cooler BC/BD-2X580CC1-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2X580CC1-B01 C

Heat rejection i
637.32 kW
Air flow
190,253 m³/h
Fans
10 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 190,253 m³/h
External surface 2,402.4 m²
Inner volume 313.1 dm³
Fin materialAluminium
Net weight 1,931 kg
Fans
Quantity 10
Diameter 800 mm
Speed 900 rpm
Power 18,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 57.0 dB(A)
Sound power 90.1 dB(A)
Energy class D
Connections
Inlet 5"
Outlet 5"
Defrost
BC/BD-2X580CC1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
637.319 kW Fluid flow 110.61 m³/h Pressure drop 25.0 kPa
Heat rejection · Low speed (Y)
497.565 kW Fluid flow 86.36 m³/h Pressure drop 15.9 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 361.99 not rated not rated not rated not rated not rated
40 637.32 364.94 not rated not rated not rated not rated
45 904.29 638.01 367.43 not rated not rated not rated
50 1168.54 903.23 638.70 369.63 not rated not rated
55 1431.41 1165.75 902.41 639.42 371.83 not rated
60 1693.62 1427.15 1163.58 901.88 640.58 374.12

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 285.48 not rated not rated not rated not rated not rated
40 497.57 287.64 not rated not rated not rated not rated
45 701.94 497.56 289.50 not rated not rated not rated
50 903.92 700.44 497.72 291.19 not rated not rated
55 1104.75 901.02 699.32 498.12 292.88 not rated
60 1304.96 1100.49 898.69 698.72 498.93 294.71

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 637.319 110.61 25.0
Low speed (Y) 497.565 86.36 15.9

Dimensions

Dimension drawing of BC/BD-2X580CC1-B01 C
Dimension drawing
Dimensions as drawn
A 9300 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 8850 mm
H 1750 mm
I 2310 mm
K 9700 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 9300 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.