Dry cooler BC/BD-2X580HA5-B01 C

Dry cooler BC/BD-2X580HA5-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2X580HA5-B01 C

Heat rejection i
267.33 kW
Air flow
188,850 m³/h
Fans
10 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 188,850 m³/h
External surface 453.9 m²
Inner volume 93.0 dm³
Fin materialAluminium
Net weight 1,184 kg
Fans
Quantity 10
Diameter 800 mm
Speed 900 rpm
Power 18,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 58.0 dB(A)
Sound power 90.2 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-2X580HA5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
267.328 kW Fluid flow 46.39 m³/h Pressure drop 23.3 kPa
Heat rejection · Low speed (Y)
221.260 kW Fluid flow 38.40 m³/h Pressure drop 16.6 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 142.89 not rated not rated not rated not rated not rated
40 267.33 145.15 not rated not rated not rated not rated
45 389.47 269.07 147.11 not rated not rated not rated
50 511.02 390.91 270.67 148.83 not rated not rated
55 632.34 512.21 392.26 272.14 150.38 not rated
60 753.51 633.32 513.41 393.59 273.53 151.79

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 118.60 not rated not rated not rated not rated not rated
40 221.26 120.51 not rated not rated not rated not rated
45 321.61 222.63 122.15 not rated not rated not rated
50 421.40 322.67 223.84 123.59 not rated not rated
55 520.92 422.21 323.67 225.00 124.91 not rated
60 620.31 521.50 423.02 324.67 226.13 126.12

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 267.328 46.39 23.3
Low speed (Y) 221.260 38.40 16.6

Dimensions

Dimension drawing of BC/BD-2X580HA5-B01 C
Dimension drawing
Dimensions as drawn
A 5600 mm
B 1450 mm
C 2310 mm
F 1150 mm
G 550 mm
E 5350 mm
H 1050 mm
I 2260 mm
K 5900 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 5600 mm
Width 2310 mm
Height 1450 mm

Downloads