Skip to Content

Dry cooler BC/BD-2X580HD5-B01 C

Dry cooler BC/BD-2X580HD5-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2X580HD5-B01 C

Heat rejection i
462.95 kW
Air flow
148,513 m³/h
Fans
10 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 148,513 m³/h
External surface 1,134.7 m²
Inner volume 191.8 dm³
Fin materialAluminium
Net weight 1,388 kg
Fans
Quantity 10
Diameter 800 mm
Speed 900 rpm
Power 18,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 61.0 dB(A)
Sound power 93.0 dB(A)
Energy class E
Connections
Inlet 5"
Outlet 5"
Defrost
BC/BD-2X580HD5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
462.948 kW Fluid flow 80.36 m³/h Pressure drop 74.5 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
359.508 kW Fluid flow 62.40 m³/h Pressure drop 47.6 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 269.75 not rated not rated not rated not rated not rated
40 462.95 271.20 not rated not rated not rated not rated
45 651.63 463.68 272.57 not rated not rated not rated
50 838.85 651.79 464.54 273.95 not rated not rated
55 1025.42 838.49 652.24 465.65 275.43 not rated
60 1211.60 1024.53 838.58 653.15 467.11 277.13

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 211.28 not rated not rated not rated not rated not rated
40 359.51 212.44 not rated not rated not rated not rated
45 503.84 360.05 213.53 not rated not rated not rated
50 646.87 503.92 360.74 214.66 not rated not rated
55 789.37 646.53 504.26 361.64 215.91 not rated
60 931.53 788.62 646.62 505.02 362.89 217.49

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 462.948 80.36 74.5
Low speed (Y) 359.508 62.40 47.6

Dimensions

Dimension drawing of BC/BD-2X580HD5-B01 C
Dimension drawing
Dimensions as drawn
A 5800 mm
B 1450 mm
C 2310 mm
F 1150 mm
G 550 mm
E 5350 mm
H 1050 mm
I 2260 mm
K 6300 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 5800 mm
Width 2310 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.