Skip to Content

Dry cooler BC/BD-2X650BA1-B09 C

Dry cooler BC/BD-2X650BA1-B09 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2X650BA1-B09 C

Heat rejection i
162.93 kW
Air flow
88,211 m³/h
Fans
12 × ⌀500 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Model nomenclature

How to read the code of this model.

  • A
    Series: BC/BD — BC = vertical, BD = horizontal dry cooler (air flow bottom to top).
  • C
    Fan rows (optional "Nx"): 2 — Catalogue: "Fan Row no." (number before x/X).
  • D
    Number of fans per row: 6 — Digit 1-9; total fans = fan rows x this digit.
  • E
    Fan diameter: 50 — Ø500 mm
  • G
    Coil tube rows (2nd dimensional letter): A — 2 tube rows
  • H
    Fin spacing: 1 — 2.1 mm
  • I
    Generation code: B — generation B
  • J
    Fan data (fan motor code): 09 — single-phase 230 V 50 Hz, 4-pole AC fan (in this series)

Data

Coil
Air flow 88,211 m³/h
External surface 355.6 m²
Inner volume 65.1 dm³
Fin materialAluminium
Net weight 623 kg
Fans
Quantity 12
Diameter 500 mm
Speed 1,330 rpm
Power 8,500 W
Supply 230V/1Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 58.0 dB(A)
Sound power 90.0 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-2X650BA1-B09 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · Single phase
162.929 kW Fluid flow 28.28 m³/h Pressure drop 14.4 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

Single phase

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 86.63 not rated not rated not rated not rated not rated
40 162.93 88.07 not rated not rated not rated not rated
45 237.42 163.80 89.27 not rated not rated not rated
50 311.43 237.93 164.57 90.33 not rated not rated
55 385.25 311.63 238.41 165.27 91.25 not rated
60 458.94 385.16 311.84 238.88 165.97 92.11

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
Single phase 162.929 28.28 14.4

Dimensions

Dimension drawing of BC/BD-2X650BA1-B09 C
Dimension drawing
Dimensions as drawn
A 5250 mm
B 1220 mm
C 1710 mm
F 1050 mm
G 450 mm
E 4900 mm
H 800 mm
I 1660 mm
K 5600 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 5250 mm
Width 1800 mm
Height 1220 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.