Skip to Content

Dry cooler BC/BD-2X663BB1-B19 C

Dry cooler BC/BD-2X663BB1-B19 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2X663BB1-B19 C

Heat rejection i
345.30 kW
Air flow
140,040 m³/h
Fans
12 × ⌀630 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 140,040 m³/h
External surface 826.7 m²
Inner volume 142.6 dm³
Fin materialAluminium
Net weight 924 kg
Fans
Quantity 12
Diameter 630 mm
Speed 1,330 rpm
Power 15,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 62.0 dB(A)
Sound power 94.1 dB(A)
Energy class E
Connections
Inlet 5"
Outlet 5"
Defrost
BC/BD-2X663BB1-B19 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
345.300 kW Fluid flow 59.93 m³/h Pressure drop 17.9 kPa
Heat rejection · Low speed (Y)
294.848 kW Fluid flow 51.18 m³/h Pressure drop 13.5 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 188.60 not rated not rated not rated not rated not rated
40 345.30 191.01 not rated not rated not rated not rated
45 497.85 346.43 193.02 not rated not rated not rated
50 649.15 498.08 347.45 194.78 not rated not rated
55 799.94 648.58 498.32 348.40 196.39 not rated
60 950.39 798.60 648.16 498.68 349.42 197.91

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 161.60 not rated not rated not rated not rated not rated
40 294.85 163.76 not rated not rated not rated not rated
45 424.00 295.79 165.55 not rated not rated not rated
50 551.96 424.13 296.62 167.10 not rated not rated
55 679.39 551.39 424.30 297.44 168.52 not rated
60 806.54 678.15 550.96 424.62 298.35 169.89

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 345.300 59.93 17.9
Low speed (Y) 294.848 51.18 13.5

Dimensions

Dimension drawing of BC/BD-2X663BB1-B19 C
Dimension drawing
Dimensions as drawn
A 5850 mm
B 1220 mm
C 2310 mm
F 1050 mm
G 450 mm
E 5500 mm
H 900 mm
I 2260 mm
K 6200 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 5850 mm
Width 2310 mm
Height 1220 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.