Skip to Content

Dry cooler BC/BD-2X663BD1-B19 C

Dry cooler BC/BD-2X663BD1-B19 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2X663BD1-B19 C

Heat rejection i
460.25 kW
Air flow
129,757 m³/h
Fans
12 × ⌀630 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 129,757 m³/h
External surface 1,377.8 m²
Inner volume 195.5 dm³
Fin materialAluminium
Net weight 1,072 kg
Fans
Quantity 12
Diameter 630 mm
Speed 1,330 rpm
Power 15,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 62.0 dB(A)
Sound power 94.0 dB(A)
Energy class E
Connections
Inlet 5"
Outlet 5"
Defrost
BC/BD-2X663BD1-B19 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
460.251 kW Fluid flow 79.88 m³/h Pressure drop 75.6 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
378.476 kW Fluid flow 65.64 m³/h Pressure drop 53.4 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 271.60 not rated not rated not rated not rated not rated
40 460.25 272.21 not rated not rated not rated not rated
45 643.88 459.54 272.79 not rated not rated not rated
50 825.96 642.05 459.04 273.39 not rated not rated
55 1007.30 823.03 640.56 458.73 274.11 not rated
60 1188.20 1003.29 820.65 639.62 458.93 275.08

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 224.97 not rated not rated not rated not rated not rated
40 378.48 225.72 not rated not rated not rated not rated
45 527.66 378.26 226.39 not rated not rated not rated
50 675.41 526.65 378.18 227.09 not rated not rated
55 822.50 673.68 525.96 378.32 227.72 not rated
60 969.21 820.06 672.39 525.62 378.49 228.55

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 460.251 79.88 75.6
Low speed (Y) 378.476 65.64 53.4

Dimensions

Dimension drawing of BC/BD-2X663BD1-B19 C
Dimension drawing
Dimensions as drawn
A 5850 mm
B 1220 mm
C 2310 mm
F 1050 mm
G 450 mm
E 5500 mm
H 900 mm
I 2260 mm
K 6200 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 5850 mm
Width 2310 mm
Height 1220 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.