BC/BD-680EC1-B01I C
339.54 kW
Defrost: None
Product code: BC/BD-2X663BD5-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 96,192 m³/h |
|---|---|
| External surface | 1,167.1 m² |
| Inner volume | 195.5 dm³ |
| Fin material | Aluminium |
| Net weight | 1,047 kg |
| Quantity | 12 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 7,200 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 85.3 dB(A) |
| Energy class | D |
| Inlet | 5" |
|---|---|
| Outlet | 5" |
| BC/BD-2X663BD5-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 200.55 | not rated | not rated | not rated | not rated | not rated |
| 40 | 339.82 | 201.16 | not rated | not rated | not rated | not rated |
| 45 | 475.26 | 339.51 | 201.74 | not rated | not rated | not rated |
| 50 | 609.55 | 474.19 | 339.33 | 202.32 | not rated | not rated |
| 55 | 743.28 | 607.77 | 473.40 | 339.39 | 202.99 | not rated |
| 60 | 876.68 | 740.78 | 606.39 | 473.00 | 339.70 | 203.85 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 339.817 | 58.98 | 44.2 |
| A | 5850 mm |
|---|---|
| B | 1220 mm |
| C | 2310 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 5500 mm |
| H | 900 mm |
| I | 2260 mm |
| K | 6200 mm |
| D IN | 5" |
| D OUT | 5" |
| Length | 5850 mm |
|---|---|
| Width | 2310 mm |
| Height | 1220 mm |
Our engineers answer with a selection for your conditions.