BC/BD-2x680DB1-B01 C
578.27 kW
Defrost: None
Product code: BC/BD-2X680DC5-B01I C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 180,948 m³/h |
|---|---|
| External surface | 1,589.8 m² |
| Inner volume | 412.8 dm³ |
| Fin material | Aluminium |
| Net weight | 1,856 kg |
| Quantity | 12 |
|---|---|
| Diameter | 800 mm |
| Speed | 880 rpm |
| Power | 23,500 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 63.0 dB(A) |
|---|---|
| Sound power | 95.1 dB(A) |
| Energy class | E |
| Inlet | 6" |
|---|---|
| Outlet | 6" |
| BC/BD-2X680DC5-B01I C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 333.78 | not rated | not rated | not rated | not rated | not rated |
| 40 | 579.01 | 335.82 | not rated | not rated | not rated | not rated |
| 45 | 818.14 | 579.74 | 337.65 | not rated | not rated | not rated |
| 50 | 1055.30 | 817.79 | 580.56 | 339.41 | not rated | not rated |
| 55 | 1291.54 | 1053.93 | 817.80 | 581.63 | 341.25 | not rated |
| 60 | 1527.22 | 1289.19 | 1053.15 | 818.29 | 583.14 | 343.30 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 579.010 | 100.50 | 29.0 |
| A | 7750 mm |
|---|---|
| B | 1450 mm |
| C | 2360 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 7300 mm |
| H | 1200 mm |
| I | 2310 mm |
| K | 8250 mm |
| D IN | 6" |
| D OUT | 6" |
| Length | 7750 mm |
|---|---|
| Width | 2360 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.