Skip to Content

Dry cooler BC/BD-2X680EC1-B01 C

Dry cooler BC/BD-2X680EC1-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2X680EC1-B01 C

Heat rejection i
706.44 kW
Air flow
198,367 m³/h
Fans
12 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 198,367 m³/h
External surface 2,189.2 m²
Inner volume 466.2 dm³
Fin materialAluminium
Net weight 2,070 kg
Fans
Quantity 12
Diameter 800 mm
Speed 900 rpm
Power 21,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 60.0 dB(A)
Sound power 92.4 dB(A)
Energy class E
Connections
Inlet 6"
Outlet 6"
Defrost
BC/BD-2X680EC1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
706.444 kW Fluid flow 122.61 m³/h Pressure drop 47.1 kPa
Heat rejection · Low speed (Y)
545.898 kW Fluid flow 94.67 m³/h Pressure drop 29.7 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 414.61 not rated not rated not rated not rated not rated
40 706.44 416.29 not rated not rated not rated not rated
45 990.48 706.50 417.91 not rated not rated not rated
50 1272.07 989.10 706.79 419.55 not rated not rated
55 1552.42 1269.33 988.31 707.44 421.39 not rated
60 1832.09 1548.38 1267.47 988.31 708.88 423.53

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 323.90 not rated not rated not rated not rated not rated
40 545.90 325.11 not rated not rated not rated not rated
45 761.46 545.75 326.31 not rated not rated not rated
50 974.82 760.17 545.89 327.57 not rated not rated
55 1187.15 972.46 759.41 546.44 328.98 not rated
60 1398.90 1183.76 970.89 759.39 547.49 330.46

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 706.444 122.61 47.1
Low speed (Y) 545.898 94.67 29.7

Dimensions

Dimension drawing of BC/BD-2X680EC1-B01 C
Dimension drawing
Dimensions as drawn
A 8950 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 8500 mm
H 1400 mm
I 2310 mm
K 9450 mm
D IN 6"
D OUT 6"
Overall [mm]
Length 8950 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.