Skip to Content

Dry cooler BC/BD-2X763BA5-B19 C

Dry cooler BC/BD-2X763BA5-B19 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2X763BA5-B19 C

Heat rejection i
279.79 kW
Air flow
171,370 m³/h
Fans
14 × ⌀630 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 171,370 m³/h
External surface 544.7 m²
Inner volume 103.2 dm³
Fin materialAluminium
Net weight 1,046 kg
Fans
Quantity 14
Diameter 630 mm
Speed 1,330 rpm
Power 17,500 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 64.0 dB(A)
Sound power 96.1 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-2X763BA5-B19 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
279.792 kW Fluid flow 48.56 m³/h Pressure drop 29.4 kPa
Heat rejection · Low speed (Y)
245.333 kW Fluid flow 42.58 m³/h Pressure drop 23.2 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 153.05 not rated not rated not rated not rated not rated
40 279.79 154.70 not rated not rated not rated not rated
45 404.16 280.78 156.12 not rated not rated not rated
50 527.91 404.65 281.62 157.34 not rated not rated
55 651.36 527.96 405.10 282.42 158.44 not rated
60 774.68 650.99 528.03 405.57 283.20 159.46

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 134.53 not rated not rated not rated not rated not rated
40 245.33 136.05 not rated not rated not rated not rated
45 353.87 246.22 137.32 not rated not rated not rated
50 461.78 354.34 247.00 138.44 not rated not rated
55 569.42 461.84 354.76 247.76 139.45 not rated
60 676.88 569.12 461.94 355.21 248.49 140.45

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 279.792 48.56 29.4
Low speed (Y) 245.333 42.58 23.2

Dimensions

Dimension drawing of BC/BD-2X763BA5-B19 C
Dimension drawing
Dimensions as drawn
A 6750 mm
B 1220 mm
C 2310 mm
F 1050 mm
G 450 mm
E 6400 mm
H 900 mm
I 2260 mm
K 7100 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 6750 mm
Width 2310 mm
Height 1220 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.