Skip to Content

Dry cooler BC/BD-2X980AC1-B01 C

Dry cooler BC/BD-2X980AC1-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2X980AC1-B01 C

Heat rejection i
938.13 kW
Air flow
294,666 m³/h
Fans
18 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 294,666 m³/h
External surface 2,965.2 m²
Inner volume 399.1 dm³
Fin materialAluminium
Net weight 2,749 kg
Fans
Quantity 18
Diameter 800 mm
Speed 900 rpm
Power 32,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 63.0 dB(A)
Sound power 95.5 dB(A)
Energy class E
Connections
Inlet 6"
Outlet 6"
Defrost
BC/BD-2X980AC1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
938.133 kW Fluid flow 162.84 m³/h Pressure drop 47.1 kPa
Heat rejection · Low speed (Y)
739.007 kW Fluid flow 128.25 m³/h Pressure drop 30.6 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 538.09 not rated not rated not rated not rated not rated
40 938.13 541.74 not rated not rated not rated not rated
45 1328.11 939.67 545.09 not rated not rated not rated
50 1714.83 1327.89 941.35 548.28 not rated not rated
55 2100.02 1712.98 1328.22 943.43 551.55 not rated
60 2484.27 2096.59 1712.10 1329.45 946.22 555.11

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 428.33 not rated not rated not rated not rated not rated
40 739.01 431.18 not rated not rated not rated not rated
45 1040.64 740.01 433.75 not rated not rated not rated
50 1339.36 1040.16 741.19 436.27 not rated not rated
55 1636.74 1337.56 1040.19 742.75 438.96 not rated
60 1933.30 1633.64 1336.61 1041.10 744.89 441.91

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 938.133 162.84 47.1
Low speed (Y) 739.007 128.25 30.6

Dimensions

Dimension drawing of BC/BD-2X980AC1-B01 C
Dimension drawing
Dimensions as drawn
A 11350 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 10900 mm
H 1200 mm
I 2310 mm
K 11850 mm
D IN 6"
D OUT 6"
Overall [mm]
Length 11350 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.