BC/BD-2X880EC1-B01I C
918.93 kW
Defrost: None
Product code: BC/BD-2X980DC5-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 284,584 m³/h |
|---|---|
| External surface | 2,384.6 m² |
| Inner volume | 572.9 dm³ |
| Fin material | Aluminium |
| Net weight | 2,742 kg |
| Quantity | 18 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 32,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 63.0 dB(A) |
|---|---|
| Sound power | 96.0 dB(A) |
| Energy class | E |
| Inlet | 6" |
|---|---|
| Outlet | 6" |
| BC/BD-2X980DC5-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 540.49 | not rated | not rated | not rated | not rated | not rated |
| 40 | 919.81 | 542.42 | not rated | not rated | not rated | not rated |
| 45 | 1290.66 | 920.28 | 544.32 | not rated | not rated | not rated |
| 50 | 1658.75 | 1289.83 | 921.03 | 546.28 | not rated | not rated |
| 55 | 2025.55 | 1656.66 | 1289.63 | 922.37 | 548.51 | not rated |
| 60 | 2391.57 | 2022.25 | 1655.53 | 1290.34 | 924.44 | 551.20 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 426.11 | not rated | not rated | not rated | not rated | not rated |
| 40 | 718.31 | 427.55 | not rated | not rated | not rated | not rated |
| 45 | 1003.20 | 718.46 | 428.96 | not rated | not rated | not rated |
| 50 | 1285.81 | 1002.31 | 718.98 | 430.52 | not rated | not rated |
| 55 | 1567.33 | 1283.90 | 1002.02 | 719.97 | 432.35 | not rated |
| 60 | 1848.21 | 1564.42 | 1282.90 | 1002.65 | 721.71 | 434.65 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 919.812 | 159.64 | 94.0 |
| Low speed (Y) | 718.305 | 124.67 | 60.5 |
| A | 11350 mm |
|---|---|
| B | 1450 mm |
| C | 2360 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 10900 mm |
| H | 1200 mm |
| I | 2310 mm |
| K | 11850 mm |
| D IN | 6" |
| D OUT | 6" |
| Length | 11350 mm |
|---|---|
| Width | 2360 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.