BC/BD-2x180KB5-B03 C
61.24 kW
Defrost: None
Product code: BC/BD-2x180AC5-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 16,795 m³/h |
|---|---|
| External surface | 278.6 m² |
| Inner volume | 40.8 dm³ |
| Fin material | Aluminium |
| Net weight | 358 kg |
| Quantity | 2 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 35.0 dB(A) |
|---|---|
| Sound power | 67.0 dB(A) |
| Energy class | C |
| Inlet | 1 1/2" |
|---|---|
| Outlet | 1 1/2" |
| BC/BD-2x180AC5-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 36.48 | not rated | not rated | not rated | not rated | not rated |
| 40 | 61.23 | 36.55 | not rated | not rated | not rated | not rated |
| 45 | 85.35 | 61.17 | 36.63 | not rated | not rated | not rated |
| 50 | 109.26 | 85.16 | 61.12 | 36.72 | not rated | not rated |
| 55 | 133.08 | 108.96 | 85.03 | 61.13 | 36.83 | not rated |
| 60 | 156.85 | 132.66 | 108.73 | 84.97 | 61.21 | 36.98 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 28.66 | not rated | not rated | not rated | not rated | not rated |
| 40 | 47.64 | 28.70 | not rated | not rated | not rated | not rated |
| 45 | 66.10 | 47.56 | 28.75 | not rated | not rated | not rated |
| 50 | 84.38 | 65.92 | 47.51 | 28.80 | not rated | not rated |
| 55 | 102.58 | 84.10 | 65.78 | 47.50 | 28.89 | not rated |
| 60 | 120.74 | 102.20 | 83.89 | 65.71 | 47.55 | 29.00 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 61.232 | 10.63 | 74.0 |
| Low speed (Y) | 47.641 | 8.26 | 47.2 |
| A | 1550 mm |
|---|---|
| B | 1450 mm |
| C | 2360 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 1300 mm |
| H | 1200 mm |
| I | 2310 mm |
| K | 1850 mm |
| D IN | 1 1/2" |
| D OUT | 1 1/2" |
| Length | 1850 mm |
|---|---|
| Width | 2360 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.